Critical Authorization Bypass & Hard‑Coded Key Flaws in Moxa AIG‑302 ThingsPro Edge Firmware (CVE‑2026‑109812, CVE‑2026‑109813)
What It Is
The U.S. Cybersecurity and Infrastructure Security Agency (CISA) has issued an Industrial Control Systems (ICS) advisory (ICS‑A‑26‑293‑03) describing two high‑severity vulnerabilities in the firmware of Moxa’s AIG‑302 ThingsPro Edge gateway (versions ≤ 1.4.0). The device is a compact, rugged edge‑computing platform that aggregates sensor data, runs containerized applications, and provides remote management for a wide range of critical‑infrastructure environments, including manufacturing, energy generation, and water‑treatment facilities worldwide.
The first flaw, catalogued as CVE‑2026‑109812, is a missing authorization issue in the internal REST API endpoint /api/v1/secrets/. The endpoint is intended to serve secret material (e.g., TLS certificates, API tokens) to privileged services running on the gateway. However, the firmware does not enforce proper access controls on requests to this path. An attacker who has already obtained a valid, low‑privilege credential—such as a user account used for routine monitoring—or who can place a malicious device on the same LAN segment (adjacent network) can issue a crafted HTTP request to the endpoint and retrieve the stored secrets without further authentication.
The second flaw, CVE‑2026‑109813, concerns the use of a hard‑coded cryptographic key within the same firmware image. The key is embedded in the binary and is used to encrypt configuration files and internal communications. Because the key is static across all devices shipped with the vulnerable firmware, any party that extracts it from a single compromised unit can decrypt the same data on any other affected gateway. This amplifies the impact of the first vulnerability: once an attacker harvests the secret payload from the API, they can also obtain the hard‑coded key, enabling decryption of historic logs, firmware updates, and any future encrypted traffic that relies on the same key.
Both vulnerabilities receive a CVSS v3.1 base score of 8.1 (High), reflecting the combination of easy exploitability (network‑adjacent access, no user interaction) and the confidentiality impact of exposing cryptographic material. The advisory notes that successful exploitation “could allow an attacker to obtain and disclose sensitive information,” but it does not confirm any active exploitation in the wild. No public proof‑of‑concept code has been released, and CISA has not listed the issue in the Known Exploited Vulnerabilities (KEV) catalog.
Moxa’s product documentation indicates that the AIG‑302 is typically deployed in environments where it bridges field‑level devices to corporate or cloud networks. In many installations, the gateway is configured with outbound Internet access for firmware updates and remote diagnostics. The advisory therefore highlights a mitigation path: firmware version 1.4.1 contains a patch that introduces proper authorization checks on the /api/v1/secrets/ endpoint and replaces the hard‑coded key with a per‑device generated secret. Moxa recommends that all customers download and apply the update via the standard OTA mechanism or, where Internet connectivity is restricted, through a manual USB‑based installation.
The advisory’s “Background” section emphasizes the breadth of the affected sectors—critical manufacturing, energy, and water/wastewater systems—underscoring the potential systemic risk if a nation‑state or organized cyber‑crime group were to weaponize the flaws. While the advisory does not name a specific threat actor, it warns that the combination of an easily reachable API and a universal cryptographic secret creates a low‑effort, high‑reward attack surface that aligns with tactics observed in recent supply‑chain and ransomware campaigns targeting industrial IoT.
Moxa’s response, as quoted in the advisory, states: “We take the security of our customers’ operations seriously and have released firmware v1.4.1 to remediate the identified issues. Customers are urged to apply the update promptly and to follow best‑practice network segmentation to limit exposure of the gateway to untrusted networks.” The company also offers a temporary mitigation for installations that cannot immediately apply the patch: disabling the /api/v1/secrets/ endpoint via the device’s configuration interface and ensuring that the gateway does not have unnecessary Internet access until the update can be installed.
The advisory concludes with standard recommendations for operators: inventory all deployed AIG‑302 units, verify firmware versions, apply the patch, and review network segmentation policies. No legal or regulatory penalties are mentioned, but the advisory notes that failure to remediate could affect compliance with sector‑specific standards such as NERC CIP for the energy sector or IEC 62443 for industrial automation.