Critical Vulnerabilities in Dorsett Controls InfoScan (CVE‑2026‑117659 – CVE‑2026‑120298) Threaten Water‑Utility OT Environments
What It Is — The U.S. Cybersecurity & Infrastructure Security Agency (CISA) issued an Industrial Control Systems Advisory (ICS‑A‑26‑321‑01) identifying six high‑severity flaws in Dorsett Controls InfoScan, a desktop‑based OT data‑collection and visualization tool used by water‑ and wastewater utilities worldwide. All vulnerabilities affect InfoScan versions ≤ 1.45.0 and share a CVSS v3 base score of 8.1 (High).
- Improper Certificate Validation (CVE‑2026‑117659) – The Electron‑based client accepts TLS certificates without verifying the trust chain, allowing a man‑in‑the‑middle (MitM) attacker to present any certificate and have the client trust it.
- Hard‑coded Cryptographic Key (CVE‑2026‑120157) – A static AES key is embedded in the binary, enabling an adversary who extracts the binary to decrypt stored credentials or configuration data.
- Missing Authentication for Critical Function (CVE‑2026‑120255) – Certain internal APIs can be invoked without any authentication, exposing functions that retrieve system logs and configuration files.
- Exposure of Sensitive System Information (CVE‑2026‑120260) – Error handling routines leak internal paths, version numbers, and environment variables to any connected client, providing reconnaissance data.
- Generation of Error Message Containing Sensitive Information (CVE‑2026‑120271) – Similar to the above, malformed requests trigger verbose stack traces that disclose usernames and service identifiers.
- Use of Insecure Electron Settings (CVE‑2026‑120298) – The client ships with
nodeIntegrationenabled,contextIsolationdisabled, andwebSecurityturned off, collapsing the browser‑process sandbox and permitting arbitrary JavaScript execution from remote content.
Collectively, these weaknesses give an attacker the ability to retrieve sensitive system information, access application data without authorization, recover stored credentials, and manipulate network communications. Exploitation does not require prior authentication; a network‑adjacent adversary who can intercept or inject traffic to the InfoScan client can trigger the chain of failures.
Affected Products – Dorsett Controls InfoScan desktop client ≤ 1.45.0 (all operating systems supported by the vendor).
Why It Matters for Trust & Control Assurance – The flaws directly violate the control objective of secure configuration and cryptographic key management, a single VCF control that maps to multiple frameworks (e.g., NIST CSF 2.0, ISO 27001). Demonstrating remediation evidence for this control strengthens audit readiness across those standards.
Recommended Actions –
- Patch Immediately – Apply the vendor‑released update (InfoScan 1.45.1 or later) that fixes all six CVEs.
- Enforce TLS Validation – Until patched, configure a network‑level TLS‑inspection proxy that validates certificates for InfoScan traffic.
- Disable Unused APIs – Block inbound calls to the unauthenticated internal endpoints via firewall rules or host‑based access controls.
- Rotate Embedded Keys – If the hard‑coded key has been used, rotate all stored credentials and re‑encrypt configuration files with a unique key per installation.
- Audit Electron Settings – Verify that
nodeIntegrationis disabled,contextIsolationenabled, andwebSecurityenforced on all client machines. - Monitor for Indicators of Compromise – Deploy IDS/IPS signatures for the known error‑message patterns and anomalous API calls.
Source: CISA Advisory ICS‑A‑26‑321‑01