Critical Stack‑Based Buffer Overflow (CVE‑2026‑129713) in Danfoss AK‑SM 8xxA Controllers Allows Remote Code Execution
What It Is — The Cybersecurity and Infrastructure Security Agency (CISA) has issued an advisory (ICS‑A‑26‑328‑03) describing a severe vulnerability in Danfoss AK‑SM 8xxA series controllers (firmware ≤ 5.4.0). The flaw is a stack‑based buffer overflow in an unauthenticated CGI handler that processes HTTP/S POST requests. By sending a specially crafted payload, an attacker can corrupt memory, force the embedded web server to restart, and potentially achieve arbitrary code execution with the same privileges as the web server process. No authentication is required, making the attack surface internet‑exposed for any device that permits remote HTTP/S access. The vulnerability carries a CVSS v3.1 base score of 9.8 (Critical) and is identified as CVE‑2026‑129713 (CWE‑121).
Affected Products — Danfoss AK‑SM 8xxA series controllers running firmware 5.4.0 or earlier (product status: known_affected).
Why It Matters for Trust & Control Assurance — This issue tests the control objective of vulnerability and patch management—the need to maintain up‑to‑date firmware and continuously monitor for unmitigated weaknesses. Verisq’s Control Mapping capability can help organizations capture evidence that this control is operating effectively across multiple frameworks.
Recommended Actions —
- Inventory all Danfoss AK‑SM 8xxA devices and verify firmware versions against the ≤ 5.4.0 threshold.
- Apply the forthcoming Danfoss 5.5.x release as soon as it becomes available; until then, consider temporary mitigations such as network segmentation and restricting inbound HTTP/S traffic to trusted sources only.
- Disable any ability for operators to turn off “Strict Mode” (future releases will enforce this by default).
- Enable intrusion detection/IPS signatures that flag anomalous POST requests to the CGI endpoint.
- Document the remediation steps and capture evidence of version compliance for audit purposes.
Source: CISA Advisory – ICSA‑26‑328‑03